Section 7. Installation
193
'Global variables (Used only outside subroutine by choice)
'Declare Counter in the Main Scan.
Public counter(2) As Long
'Declare Product of PI * counter(2).
Public pi_product(2) As Float
'Global variable (Used only in subroutine by choice)
'For / Next incrementor used in the subroutine.
Public i_sub As Long
'Declare Data Table
DataTable(pi_results,True,-1)
Sample(1,counter(),IEEE4)
EndTable
'Declare Subroutine
'Declares j(4) as local array (can only be used in subroutine)
Sub ProcessSub (j(2) As Long,OutVar(2) As Float)
For i_sub = 1 To 2
j(i_sub) = j(i_sub) + 1
'Processing to show functionality
OutVar(i_sub) = j(i_sub) * 4 * ATN(1) '(Tip: 4 * ATN(1) = pi to IEEE4 precision)
Next i_sub
EndSub
BeginProg
counter(1) = 1
counter(2) = 2
Scan(1,Sec,0,0)
'Pass Counter() array to j() array, pi_pruduct() to OutVar()
Call ProcessSub (counter(),pi_product())
CallTable pi_results
NextScan
EndProg
7.8.5 Wind Vector
The WindVector() instruction processes wind-speed and direction measurements
to calculate mean speed, mean vector magnitude, and mean vector direction over a
data storage interval. Measurements from polar (wind speed and direction) or
orthogonal (fixed East and North propellers) sensors are supported. Vector
direction and standard deviation of vector direction can be calculated weighted or
unweighted for wind speed.
7.8.5.1 OutputOpt Parameters
In the CR3000 WindVector() instruction, the OutputOpt parameter defines the
processed data that are stored. All output options result in an array of values, the
elements of which have _WVc(n) as a suffix, where n is the element number. The
array uses the name of the Speed/East variable as its base. table OutputOpt
Options
(p. 194) lists and describes OutputOpt options.