CS11-L Current Transformer
Measurement Ranges: 0.15 to 200 A (0.15 to 125 A for CR200X)
Frequency: 50 and 60 Hz
Insulation Resistance: 100 M ohm @ 500 Vdc
High Potential: 2000 volts
Rated Current: 200 A, 125 A (CR200X)
Storage Temperature: –25º to 70ºC
Operating Temperature: –25º to 55ºC
Case Material: Polypropylene Resin
Construction: Epoxy Encapsulated
Accuracy with 10 ohm
Burden Max. (resistive): Typically ±1 percent of actual value with
provided multiplier
Dimensions
Outer Diameter: 4.8 cm (1.89 in)
Inner Diameter: 1.9 cm (0.75 in)
Height: 1.7 cm (0.67 in)
Multiplier: i
Mult
=200 A/1000mV=0.2
3. Installation
Place one AC wire through the hole of the CS11-L (see FIGURE 3-1). The
sensor may be placed on either the hot or neutral AC wire.
FIGURE 3-1. AC load wire installed in CS11-L (color of ac load wire
can vary)