Campbell-scientific CR800 and CR850 Measurement and Control Systems Uživatelský manuál Strana 415

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 566
  • Tabulka s obsahem
  • ŘEŠENÍ PROBLÉMŮ
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 414
Section 10. Troubleshooting
415
10.5.2 Troubleshooting Power at a Glance
Symptoms:
PossiblesymptomsincludetheCR800programnotexecuting;
Low12VCountoftheStatustabledisplayingalargenumber.
Affected Equipment:
Batteries,charger/regulators,solarpanels,transformers
Likely Cause:
Batteriesmayneedtobereplacedorrecharged;charger/regulators
mayneedtobefixedorrecalibrated;solarpanelsortransformersmay
needtobefixedorre
placed.
Required Equipment:
Voltmeter;5kΩresistoranda50‐Ω1Wresistorforthechargingcircuit
testsandtoadjustthechargingcircuitvoltage.
10.5.3 Diagnosis and Fix Procedures
10.5.3.1 Battery Test
The procedure outlined in this flow chart tests sealed-rechargeable or alkaline
batteries in the PS100 charging regulator, or a sealed-rechargeable battery
attached to a CH100 charging regulator. If a need for repair is indicated after
following the procedure, see Warranty and Assistance
(p. 3) for information on
sending items to Campbell Scientific.
Zobrazit stránku 414
1 2 ... 410 411 412 413 414 415 416 417 418 419 420 ... 565 566

Komentáře k této Příručce

Žádné komentáře