Model 109 Temperature Probe
FIGURE 6-2. Steinhart-Hart linearization error
7. Installation
If you are programming your datalogger with Short Cut, skip Section 7.1,
Wiring to Datalogger, and Section 7.2, Datalogger Programming. Short Cut
does this work for you. See Section 4, Quickstart, for a Short Cut tutorial.
7.1 Wiring to Datalogger
Wire Color Wire Function
Datalogger Connection
Terminal
Black Voltage-excitation input
U configured for voltage
excitation
1
, EX, VX
(voltage excitation)
Red Analog-voltage output
U configured for single-ended
analog input
1
, SE
(single-ended,
analog-voltage input)
Purple Bridge-resistor lead
AG or
(analog ground)
Clear EMF shield
AG or
(analog ground)
1
U channels are automatically configured by the measurement instruction.
-0.005
0
0.005
0.01
0.015
0.02
0.025
0.03
-50 -40 -30 -20 -10 0 10 20 30 40 50 60 70
Error °C
Temperature °C
Steinhart-Hart Linearization Error
6
Zobrazit stránku 13