RAWS-F Remote Automated Weather Station for Fire Weather
FIGURE 4-2. Rain gage and CS300-QD pyranometer
4.3.2 Wiring
The TE525-LQ attaches to the connector labeled PRECIP, which is color
coded blue. This sensor is internally wired from the RAWS connector panel to
the CR1000.
TABLE 4-2. PRECIP Connector (color coded blue)
Connector Pin Description CR1000 Terminal
A Tipping Bucket C6
B 5 V 5V
C Ground G
4.3.3 Maintenance
The rain gage funnel and bucket mechanism must be kept clean. Routinely
check for and remove any foreign material, dust, insects, etc.
4.3.4 Calibration
Recalibrate the rain gage annually. Obtain an RMA number before returning
this sensor to Campbell Scientific for recalibration.