CS700 and CS700H Rain Gage
4.2 CS700H Heated Rain Gage Connections
The CS700H sensor cable can be wired to the datalogger’s pulse channels (see
Table 4-3). The sensor cable can also be wired to the datalogger control ports
instead of pulse channels (see Table 4-4).
TABLE 4-3. CS700H Sensor Cable Wiring for Pulse Channel Inputs
Color
Description
CR800, CR850,
CR1000,
CR3000,
CR5000
CR10X, CR23X
Green SDI-12 SDI-12
compatible
Control Port
(e.g., C1,
C3, C5, C7)
SDI-12
compatible
Control Port
(e.g., C1-C8)
Red 12V 12V 12V
Black 0V G G
Blue Signal A Pulse Channel
(e.g., P1, P2)
Pulse Channel
(e.g., P1, P2)
White Signal Reference
G
Yellow Signal B Pulse Channel
(e.g., P1, P2)
Pulse Channel
(e.g., P1, P2)
Brown Signal Return
G
TABLE 4-4. CS700H Sensor Cable Wiring for Control Port Inputs
Color
Description
CR800, CR850,
CR1000,
CR3000,
CR5000
CR10X, CR23X
Green SDI-12 SDI-12
compatible
Control Port
(e.g., C1,
C3, C5, C7)
SDI-12
compatible
Control Port
(e.g., C1-C8)
Red 12V 12V 12V
Black 0V G G
Blue Signal A Control Port
(e.g., C1-C8)
Control Port
(e.g., C1-C8)
White 5V 5V 5V
Yellow Signal B Control Port
(e.g., C1-C8)
Control Port
(e.g., C1-C8)
Brown 5V 5V 5V
10