SDM-CD16S 16 Channel Solid State DC Control Module1/08Copyright © 2000-2008Campbell Scientific, Inc.
SDM-CD16S 16 Channel Solid State DC Control Module TABLE 1. Datalogger to SDM-CD16S Connections SDM-CD16S Datalogger Function Logic Power 12 V on
SDM-CD16S 16 Channel Solid State DC Control Module TABLE 2. Switch Position and Addresses Switch Setting Base 10 Address CRBasic Dataloggers Base 4
SDM-CD16S 16 Channel Solid State DC Control Module CDCtrl(32) would be sent to port 16 on the second SDM-CD16AC. If the Source parameter is defined
SDM-CD16S 16 Channel Solid State DC Control Module Instruction 29 – SDM-CD16S used with older CR7s Parameter Type Description 1 2 Reps (No. of modu
SDM-CD16S 16 Channel Solid State DC Control Module 8. Program Examples 8.1 Control Temperature and Fans – CR1000 In this example, the SDM-CD16S is u
SDM-CD16S 16 Channel Solid State DC Control Module The Example 1 program uses an array of values to set the SDM-CD16S control outputs: Program name: S
SDM-CD16S 16 Channel Solid State DC Control Module The Example 2 program uses an integer instead of an array to set the SDM-CD16S control outputs: &ap
SDM-CD16S 16 Channel Solid State DC Control Module Input Location assignments are as follows: Input Location Location Label Description 1..5 Temp #1
SDM-CD16S 16 Channel Solid State DC Control Module 9: Else (P94) Else, If the heater is off, 10: Z=F (P30) 1: 0 F Enter a "0&q
SDM-CD16S 16 Channel Solid State DC Control Module START FAN CONTROL LOGIC BASED ON HEATER/COOLER 22: If X<=>F (P89) If heater is on 1: 10-
Warranty and Assistance The SDM-CD16S 16 CHANNEL SOLID STATE DC CONTROL MODULE is warranted by CAMPBELL SCIENTIFIC, INC. to be free from defects in ma
SDM-CD16S 16 Channel Solid State DC Control Module 33: Beginning of Loop (P87) Start fan loop 1: 0 Delay 2: 5 Loop Count 34: Z=F (P30)
SDM-CD16S 16 Channel Solid State DC Control Module The SiteSequence array also allows a site to be measured multiple times within the sequence. For s
SDM-CD16S 16 Channel Solid State DC Control Module 'CR1000 Series Datalogger 'CR1000 Wiring: 'SDM Connections 'C1 SDM Data (
SDM-CD16S 16 Channel Solid State DC Control Module DataTable (SiteAvg,True,3000) DataInterval (0,30,Sec,10) CardOut(0,50000) Sample (1,SiteOutput,I
SDM-CD16S 16 Channel Solid State DC Control Module EndIf Site = SiteSequence(SeqIndex) EndIf SiteValveCD16 = SiteValve(Site) EndOmit = C
SDM-CD16S 16 Channel Solid State DC Control Module In the example in Section 8.3, the logic that controls the SDM-CD16 is in the processing task. In
SDM-CD16S 16 Channel Solid State DC Control Module 2. The sequence continues running as if nothing happened until the next occurrence of the sync int
SDM-CD16S 16 Channel Solid State DC Control Module Public OmitCounts(8) As Long Dim I As Long Dim One DataTable (RawData,True,-1) DataInterval (0,0,
SDM-CD16S 16 Channel Solid State DC Control Module 24 'Load Sequence Timing Array For I = 1 To 10 'Load the Valve and Timing Array w
This is a blank page.
SDM-CD16S Table of Contents PDF viewers note: These page numbers refer to the printed version of this document. Use the Adobe Acrobat® bookmarks tab
Campbell Scientific Companies Campbell Scientific, Inc. (CSI) 815 West 1800 North Logan, Utah 84321 UNITED STATES www.campbellsci.com info@campbells
SDM-CD16S Table of Contents ii Tables 1. Datalogger to SDM-CD16S Connections... 6 2. Switch Position
SDM-CD16S 16 Channel Solid State DC Control Module FIGURE 1. SDM-CD16S Face Panel 1. Function The SDM-CD16S has 16 DC voltage outputs that can be s
SDM-CD16S 16 Channel Solid State DC Control Module Edlog dataloggers that support SDM-CD16 devices, I/O Instruction 104 is used (some old CR7s may use
SDM-CD16S 16 Channel Solid State DC Control Module FIGURE 2. Equivalent Output Driver Circuit 3. Power Considerations The SDM-CD16S power requireme
SDM-CD16S 16 Channel Solid State DC Control Module EXTERNAL7 TO 48 VDC+ —SDM-CD16SDATALOGGERGNDC1C2C3 Connection with External Supply SDM-C
SDM-CD16S 16 Channel Solid State DC Control Module For datalogger connections, see Table 1. Multiple SDM-CD16Ss may be wired in parallel by connecting