Section 9. Calibration and Zeroing
The following values of the mode variable are used to initiate a calibration
process:
1 Start the calibration, OR start the first point of a two point calibration
4 Start the second point of a two point calibration
For Zeroing and Offset calibration, a mode value of 4 is never
used. The entire calibration process is initiated with the mode
value being set to 1.
NOTE
By properly changing the known value variables and the mode variables in a
calibrating program, a manual calibration can be performed on a sensor. Steps
for doing this are given below.
9.4.2 Using the Mode Variable for Manual Single-Point
Calibration
These steps demonstrate how to perform manual single-point calibrations
(Zeroing or Offset calibrations):
1. Ensure the status (value of the mode variable) is 0 or 6 before you start.
a. A number greater than 0 that is not 6 indicates that a calibration is in
progress or that the last calibration did not complete properly.
b. A number less than 0 indicates that the calibration process
encountered an error. Resolve the error before proceeding with the
calibration then set the mode value to zero for a fresh start.
2. Place the sensor into the zeroing or offset condition.
3. Indicate the known offset value (if applicable) by changing the “known
value” variable to that value.
4. Set the mode variable to 1 to initiate the calibration process.
5. Note that the datalogger automatically sets the mode variable to 2 during
the calibration process.
6. Note that the mode variable is set to 6 automatically by the datalogger
when the calibration process completes.
9.4.3 Using the Mode Variable for Manual Two-Point Calibration
These steps demonstrate how to perform manual two-point calibrations
(Multiplier/Offset or Multiplier Only):
1. Ensure the status (value of the mode variable) is 0 or 6 before you start.
a. A number greater than 0 that is not 6 indicates that a calibration is in
progress or that the last calibration did not complete properly.
9-7
Zobrazit stránku 260
1 2 ... 256 257 258 259 260 261 262 263 264 265 266 ... 367 368

Komentáře k této Příručce

Žádné komentáře

Muvit MUSLI0536 manuals

Owner’s manuals and user’s guides for Mobile phone cases Muvit MUSLI0536.
We providing 1 pdf manuals Muvit MUSLI0536 for download free by document types: Datasheet


Muvit MUSLI0536 Datasheet (1 pages)


Brand: Muvit | Category: Mobile phone cases | Size: 0.06 MB |

 




More products and manuals for Mobile phone cases Muvit

Models Document Type
MUSLI0537 Datasheet   Muvit MUSLI0537 mobile phone case, 1 pages
MUCUN0280 Datasheet   Muvit MUCUN0280 mobile phone case, 1 pages
MUSLI0525 Datasheet   Muvit MUSLI0525 mobile phone case, 1 pages
MUCUN0284 Datasheet   Muvit MUCUN0284 mobile phone case, 1 pages
MUSLI0606 Datasheet   Muvit MUSLI0606 mobile phone case, 1 pages
SEBMC0039 Datasheet   Muvit SEBMC0039 mobile phone case, 1 pages
MUCUN0285 Datasheet   Muvit MUCUN0285 mobile phone case, 1 pages
MUSLI0465 Datasheet   Muvit MUSLI0465 mobile phone case, 1 pages
SESLI0086 Datasheet   Muvit SESLI0086 mobile phone case, 1 pages
MUCUN0281 Datasheet   Muvit MUCUN0281 mobile phone case, 1 pages
MUMAG0006 Datasheet   Muvit MUMAG0006 mobile phone case, 1 pages
MUCUN0232 Datasheet   Muvit MUCUN0232 mobile phone case, 1 pages
MUCUN0278 Datasheet   Muvit MUCUN0278 mobile phone case, 1 pages
MUSNS0072 Datasheet   Muvit MUSNS0072 mobile phone case, 1 pages
MUSNS0003 Datasheet   Muvit MUSNS0003 mobile phone case, 1 pages
MUCUN0227 Datasheet   Muvit MUCUN0227 mobile phone case, 1 pages
MUCUN0229 Datasheet   Muvit MUCUN0229 mobile phone case, 1 pages
MUSLI0542 Datasheet   Muvit MUSLI0542 mobile phone case, 1 pages
MUSLI0563 Datasheet   Muvit MUSLI0563 mobile phone case, 1 pages
MUSLI0303 Datasheet   Muvit MUSLI0303 mobile phone case, 1 pages