Campbell-scientific MD485 RS-485 Multidrop Interface Uživatelský manuál Strana 13

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 68
  • Tabulka s obsahem
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 12
MD485 RS-485 Multidrop Interface
Current dataloggers and wiring panels (not mentioned in Table 2) provide
12 V on pin 8. For older products not listed, check for 12 V between
CS I/O connector pin 8 and pin 2 (GND) or contact Campbell Scientific.
b. Use default settings of MD485.
Step 3 – Connect Base MD485 to Remote MD485
a. Connect the CABLE2TP cable from the 3-pin terminal block on the Base
MD485 to the 3-pin terminal block on the Remote MD485 as described in
Section 3.3.
Step 4 – PC400/LoggerNet/PC208W Set-up
a. The next step is to run PC400/LoggerNet/PC208W and configure it to
connect to the datalogger via the MD485 point-to-point network you have
set up. The MD485 in a point-to-point network can operate transparent to
PC400/LoggerNet/PC208W. Using the EZSetup Wizard in PC400 or
LoggerNet, transparent communications is set up as if it is a direct
connect. If not using the EZSetup Wizard, simply add a datalogger to a
COM port in the Device Map.
FIGURE 5. Point-to-Point LoggerNet Network Map
7
Zobrazit stránku 12
1 2 ... 8 9 10 11 12 13 14 15 16 17 18 ... 67 68

Komentáře k této Příručce

Žádné komentáře